DCL Version 1.1
Version 1.1 introduces a datasheet-based CDU modelling approach and improves simulation robustness in the liquid-cooled rack row examples.
New features🔗
- ε–NTU base classes —
EpsNTUNominal_LiquidToLiquidandEpsNTUNominal_LiquidToAir, parameterized from a single nominal operating point. UA is derived directly from five datasheet values (cooling capacity and four temperatures) — no internal geometry required. - CDU_Nominal — new CDU variant using
EpsNTUNominal_LiquidToLiquidto size the internal heat exchanger from datasheet nominal conditions. - Product test benches — three
CDU_Nominalcomponent examples parameterized from real manufacturer datasheets: Motivair MCDU-50 (806 kW), Airedale CDU-10 (1028 kW), and Vertiv Liebert XDU1350-W2 (1320 kW).
Improvements🔗
- Improved simulation robustness of